| LXW serials vortex flowmeter is a patent right product of shanghai yinuo instrument Co.,Ltd. LXW serials vortex flowmeter is manufactured according to the principle of Kamen vortex flow. |
 | |
 |
|
●Compact structure, ●No moving parts, so has long lifetime ●Has long time stability ●Same sensor can measure liquid, gas and steam ●Whithin Reynold No. Range, meter coefficient no influence with the change of temperature,pressure, viscosity and others. ●Reynolds No. Range:2X104-7X106(For DN25-DNl00)4X104-7X106(For DNl50--DN300) ●Display: Instant and total Flow Local LCD Display ●Working Pressure:1.6~32MPa ●Fluid Temp.:—40℃~+150(Integral Type) —40℃~+300(Separate Type) ●Power:24VDC ±10% Or 3.6VDC inner lithium Battery ●Ambient Temp.:-25℃~+60℃ ●Relative Humidity:5%~95% ●Atmospheric Pressure:86~106KPa ●Measured Fluid: Liquid, Gas and Steam ●Accuracy:1%(For Liquid),1.5%(For Gas and Steam) ●Output Signal:4—20mA Current(2 Wire System) Or Standard Pulse Output(3 Wire System) ●Anti-explosion Grade: ExdIIBT4 ●Anti-explosion Certificate No.:2022346 |
| |
 |
|
Put a drum vertically into a burette and let some fluid flow down along the drum, by two sides of which there formed, in rotation, regular vortexes , which is called the Karman Street. A output frequency of the Karman Street is related to fluid velocity and drum diameter, which can be described by following formula:
f =St·v/d
Where,
f-Output frequency of the Karman Street St-Coefficient (called as Strohar number) v-velocity d-Diameter of drum
As a output frequency of the Karman Street f is direct proportional to a velocity v, It may work out an instantaneous flow rate by using a tested output frequency of the Karman Street. The Strohar number is a key coefficient for vortex street flow meters. Within the lineal section of the curve, where St≈0.17, the output frequency is direct proportional to the flow velocity, so a velocity v is derivable by using a tested frequency f. LXW serials vortex street flow transducers detect the output frequency by using piezoeletricial elements inside the sensors (probes) to test the stress that is alternatively acted on the elements by vortex. | |
 |
|
DN(mm)
|
Normal Flow Range(m3/h) |
Max.Flow Range(m3/h) |
|
Water |
Gas |
Water |
Gas |
|
25 |
2.5~13 |
25~135 |
2~17 |
20~135 |
|
40 |
3~30 |
40~338 |
2.6~40 |
35~338 |
|
50 |
5~50 |
60~547 |
4~70 |
45~547 |
|
80 |
10~100 |
90~1050 |
6~140 |
75~1050 |
|
100 |
17~170 |
170~1800 |
10~240 |
130~1715 |
|
150 |
27~360 |
350~4050 |
22~540 |
300~4050 |
|
200 |
60~650 |
600~7250 |
40~900 |
600~7275 |
|
250 |
100~1100 |
1100~11000 |
70~1200 |
1000~12000 |
|
300 |
160~1700 |
1600~17000 |
120~1600 |
1500~17000 |
Note: The outfactory calibrated fluid is water or air. | |
 |
|
|
Flow Range
|
Flow Range(kg/h) |
|
0.1MPa |
0.2MPa |
0.4MPa |
0.6MPa |
0.8MPa |
1.0MPa |
1.5MPa |
2.0MPa |
2.5MPa |
|
25
|
Min. |
20.5 |
21.5 |
25.8 |
30.5 |
34.5 |
37.9 |
45.0 |
51.8 |
57.5 |
|
Max. |
151 |
220 |
356 |
488 |
619 |
756 |
1075 |
1398 |
1720 |
|
40 |
|
34.5 |
41.3 |
53.2 |
62.2 |
70.3 |
80.3 |
107.2 |
132.8 |
157.6 |
|
|
360 |
526 |
849 |
1159 |
1485 |
1786 |
2566 |
3345 |
4122 |
|
50 |
|
57.8 |
69.5 |
89.7 |
104.5 |
118.2 |
130.8 |
157.2 |
179.3 |
197.6 |
|
|
596 |
870 |
1396 |
1928 |
2440 |
2964 |
4256 |
5538 |
6840 |
|
80
|
|
113.3 |
137 |
173 |
203 |
228 |
252 |
302 |
363 |
430 |
|
|
1150 |
1680 |
2706 |
3724 |
4720 |
5728 |
8208 |
10640 |
13100 |
|
100
|
|
195 |
238 |
302 |
355 |
398 |
457 |
610 |
754 |
893 |
|
|
2000 |
2930 |
4730 |
6500 |
8250 |
9970 |
14250 |
18620 |
22900 |
|
150
|
|
430 |
522 |
696 |
898 |
1090 |
1276 |
1694 |
2100 |
2475 |
|
|
4398 |
6420 |
10260 |
14240 |
18050 |
21850 |
31250 |
40850 |
45600 |
|
200
|
|
895 |
1085 |
1330 |
1716 |
2057 |
2398 |
3215 |
3938 |
4653 |
|
|
7870 |
11400 |
18500 |
25500 |
32300 |
39200 |
53500 |
55300 |
57000 |
|
250
|
|
1587 |
1948 |
2422 |
3120 |
3776 |
4400 |
5870 |
7257 |
8588 |
|
|
12168 |
17760 |
28652 |
39339 |
49917 |
60434 |
86636 |
107340 |
139400 |
|
300
|
|
2274 |
2839 |
4162 |
4450 |
5400 |
6300 |
8400 |
10300 |
12300 |
|
|
17428 |
25430 |
41030 |
56330 |
71480 |
86550 |
124000 |
161700 |
199600 | |
 |
| Wafer Connection Type(See below table and picture) |
Flange Connection Type(See below table and picture) |
|
DN |
A |
Φc |
ΦD |
L |
Weight(kg) |
|
Φ25 |
189.5 |
51 |
25 |
70 |
3.2 |
|
Φ40 |
197 |
73 |
40 |
70 |
4 |
|
Φ50 |
197.5 |
92 |
50 |
75 |
5.5 |
|
Φ80 |
224.5 |
127 |
70 |
100 |
9 |
|
Φ100 |
233 |
157 |
94 |
120 |
12 |
|
|
DN |
A |
ΦD |
L |
Weight(kg) |
|
Φ150 |
246 |
139 |
270 |
33 |
|
Φ200 |
269 |
186 |
310 |
45 |
|
Φ250 |
292 |
231 |
370 |
70 |
|
Φ300 |
315 |
276 |
400 |
100 |
| |
 |
|
Connection Pipe Form |
Least requirement of straight pipe |
|
Upper flow |
Down flow |
|
Concentric shrink pipe |
15D |
5D |
|
|
35D |
5D |
|
One 90°jointer pipe |
20D |
5D |
|
Two same plane 90°jointer pipe |
25D |
5D |
Two differ plane 90°jointer pipe |
30D |
5D |
|
Full open valve |
20D |
5D |
|
Half-open valve |
40D |
5D |
|
Note: D-Means the nominal diameter of flowmeter If need install temperature sensor and/or pressure sensor in the pipe system, the sensor should install the down flow of the flowmeter as the below picture shows.
|
|
| |
|
|
|
 |
|
Type |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
Note: |
| |
DN |
Transmitter |
|
|
|
|
|
|
|
LXW
|
|
|
|
|
|
|
|
|
|
Vortex Flowmeter |
|
02 |
|
|
|
|
|
|
|
DN:25mm |
|
03 |
|
|
|
|
|
|
|
DN:32mm |
|
04 |
|
|
|
|
|
|
|
DN:40mm |
|
05 |
|
|
|
|
|
|
|
DN:50mm |
|
06 |
|
|
|
|
|
|
|
DN:65mm |
|
08 |
|
|
|
|
|
|
|
DN:80mm |
|
10 |
|
|
|
|
|
|
|
DN:100mm |
|
12 |
|
|
|
|
|
|
|
DN:125mm |
|
15 |
|
|
|
|
|
|
|
DN:150mm |
|
20 |
|
|
|
|
|
|
|
DN:200mm |
|
25 |
|
|
|
|
|
|
|
DN:250mm |
|
30 |
|
|
|
|
|
|
|
DN:300mm |
|
|
ZY |
|
|
|
|
|
|
Liquid |
|
|
ZQ |
|
|
|
|
|
|
Gas or Steam |
|
|
FL |
|
|
|
|
|
|
Separate Type for Liquid, gas or Steam |
|
|
|
1 |
|
|
|
|
|
Nominal Pressure:2.5Mpa |
|
|
|
2 |
|
|
|
|
|
Nominal Pressure:4.0Mpa |
|
|
|
|
J |
|
|
|
|
Wafer Connection |
|
|
|
|
F |
|
|
|
|
Flange Connection |
| |
|
|
|
|
|
A |
|
|
|
General |
| |
|
|
|
B |
|
|
|
Anti-explosion |
| |
|
|
|
|
F |
|
|
Pulse Output |
| |
|
|
|
|
I |
|
|
4-20mA Output |
| |
|
|
|
|
|
W |
|
Power:24VDC |
| |
|
|
|
|
|
N |
|
Lithium Battery:3.6VDC |
| |
|
|
|
|
|
|
O |
No Local Display |
| |
|
|
|
|
|
|
X |
With local instant and total flow LCD display | |
| Example:LXW05-ZYJBI Means:DN:50mm,Measure fluid,Wafer Type Connection, Anti-explosion type, 4-20mA Current Output | |
 |
1.Nominal Diameter:DN_____mm 2.Fluid Name:_________________________ 3.Flow :Max.:_____ m3/h Normal_______ m3/h Min._______m3/h 4.Fluid Temp.: __________℃ 5.Working Pressure: __________MPa 6.Fluid Density:_________________g/cm3 7.Output Signal:_________________ |
|
Company: |
Shanghai Yinuo Instrument Co., Ltd. |
|
Address: |
No.7508 North Jiasong Road, Huangdu Town, Jiading District, Shanghai |
|
Postcode: |
201804 |
|
Tel: |
0086-21-5959 8313 0086-21-5959 8312 |
|
Fax: |
0086-21-5959 8113 |
|
Website: |
http://www.yinuochina.com |
|
E-Mail: |
shynyb@yahoo.com.cn 59598312@163.com |
|
Mobile Phone: |
0086-137 8890 0279 |
|
Contacter: |
Steven Shao (Sales Manager) 邵仲文 | |